Cable Connector

Mar 10, 2021

Leave a message

1. When installing the cable terminal, the semi-conductive shielding layer must be stripped off, and the insulation must not be damaged during operation. Knife marks and unevenness should be avoided. If necessary, sandpaper should be used to smooth it; the shielding end should be flat and graphite The layer (carbon particles) is removed.


2. The copper shield and steel armor of the plastic insulated cable end must be well grounded. This principle should also be followed for short circuits to avoid induced electromotive force at the end of the steel armor during unbalanced three-phase operation, and even "fire" and burn the sheath. Wait for the accident. The grounding lead wire should be tinned braided copper wire, and soldering iron should be used when connecting with the copper tape of the cable. It is not suitable to use a blowtorch to seal and solder, so as not to burn the insulation.


3. The three-phase copper shield should be connected to the ground wire separately. Note that the shield ground wire and the steel armor ground wire should be led out separately and insulated from each other. The position of the welding ground wire should be as low as possible.